Deyeb DEYEB HB-7.6-8K-1P hybrid inverters
← Back to catalogue

DEYEB HB-7.6-8K-1P

Hybrid inverter · 7.6–8 kW · single phase

Hybrid Inverters7.6–8 kWSingle phase
Request a price

Technical specifications

Battery Input Data

ParameterHB-7.6-8K-1P/AHB-7.6-8K-1P/B
Battery TypeLead-acid or Lithium-ionLead-acid or Lithium-ion
Battery Voltage Range(V)40-6040-60
Max.Charging/Discharging Current(A)190190
Charging Strategy for Li-ion BatterySelf-adaption to BMSSelf-adaption to BMS
Number of battery input11

PV String Input Data

ParameterHB-7.6-8K-1P/AHB-7.6-8K-1P/B
Max. PV Access Power (W)1520016000
Max. PV Input Power (W)988010400
Max. PV Input Voltage (V500500
Start-up Voltage(V)125125
MPPT Voltage Range(V)150-425150-425
Rated PV Input Voltage (V)370370
Max. Operating PV Input Current(A)22+2222+22
Max. Input Short-Circuit Current(A)28+2828+28
No.of MPP Trackers/No.of String Per MPP Tracker2/2+22/2+2

AC Input/Output Data

ParameterHB-7.6-8K-1P/AHB-7.6-8K-1P/B
Rated AC Input/Output Active Power(W)76008000
Max. AC Input/Output Apparent Power (VA)83608800
Rated AC Input/Output Current(A)34.5/3336.4/34.8
Max. AC Input/Output Current(A)38/36.340/38.3
Max. Continuous AC Passthrough (grid to load)(A)5050
Peak Power (off-grid)(W)2 times of rated power,10s2 times of rated power,10s
Rated Input/Output Voltage/Range(V)220/230V 0.85Un-1.1Un220/230V 0.85Un-1.1Un
Grid Connection FormL+N+PEL+N+PE
Power Factor Adjustment Range0.8 leading to 0.8 lagging0.8 leading to 0.8 lagging
Rated Input/Output Grid Frequency/Range(Hz)50/45-55, 60/55-6550/45-55, 60/55-65
Total Current Harmonic Distortion THDi<3% (of nominal power)<3% (of nominal power)
DC Injection Current<0.5%ln<0.5%ln

Efficiency

ParameterHB-7.6-8K-1P/AHB-7.6-8K-1P/B
Max Efficiency97.6%97.6%
Euro Efficiency96.5%96.5%
MPPT Efficiency>99%>99%

Equipment Protection

ParameterHB-7.6-8K-1P/AHB-7.6-8K-1P/B
IntegratedDC Polarity Reverse Connection Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Overvoltage Load Drop Protection, Ground Fault Current Monitoring, Arc Fault Circuit Interrupter (optional), Power Network Monitoring, Island Protection Monitoring, Earth Fault Detection, DC Input Switch, DC Terminal Insulation Impedance Monitoring, Residual Current (RCD) Detection, Surge protection levelDC Polarity Reverse Connection Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Overvoltage Load Drop Protection, Ground Fault Current Monitoring, Arc Fault Circuit Interrupter (optional), Power Network Monitoring, Island Protection Monitoring, Earth Fault Detection, DC Input Switch, DC Terminal Insulation Impedance Monitoring, Residual Current (RCD) Detection, Surge protection level
Surge Protection LevelTYPE II(DC),TYPE II(AC)TYPE II(DC),TYPE II(AC)

Interface

ParameterHB-7.6-8K-1P/AHB-7.6-8K-1P/B
LCD/LED DisplayLCDLCD
Communication InterfaceWIFI, RS485, CANWIFI, RS485, CAN

General Data

ParameterHB-7.6-8K-1P/AHB-7.6-8K-1P/B
Operating Temperature Range-40 to +60℃, >45℃ Derating-40 to +60℃, >45℃ Derating
Permissible Ambient Humidity0~100%0~100%
Permissible Altitude2000m2000m
Noise(dB)<30<30
Ingress Protection(IP) RatingIP 65IP 65
Inverter TopologyNon-Isolated (solar), Isolated (battery)Non-Isolated (solar), Isolated (battery)
Over Voltage CategoryOVC II(DC),OVC III(AC)OVC II(DC),OVC III(AC)
Cabinet size(W*H*D)[mm]420×670×233(Excluding Connectors and Brackets)420×670×233(Excluding Connectors and Brackets)
Weight[kg]3030
Warranty5 Years/10 Yearsthe Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy5 Years/10 Yearsthe Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy
Type Of CoolingIntelligent air coolingIntelligent air cooling
Grid RegulationIEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G98, G99, VDE-AR-N 4105IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G98, G99, VDE-AR-N 4105
Safety EMC/StandardIEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2